|
Fixed fuel systems.
The watertight nature of boats means that they also
act as good containers for leaks or overflows of flammable liquids
and vapours!
Stored fuels such as diesel or petrol in confined and
undrained spaces carry the risk of providing fuel for a fire or
explosion. This chapter covers the need to keep fuel away from
sources of ignition for as long as possible. It also covers why the
fuel filling and fuel supply arrangemen ts must not allow leaks to accumulate inside the
confines of your boat. Thus, all fuel system components must be in
good condition. They must also be fire resistant, suitable for the
fuel being used and kept away or shielded from sources of heat. To
avoid pollution, spilt fuel oils are normally prevented from being
discharged into the waterway and the detail of prevention is also
included. However, the overriding need to minimise the risk of
fires, spread of fire and explosions, means that small amounts of
overflowing fuel are better directed overboard than allowed to flow
into the craft interior. These requirements and checks apply to all
boats with inboard engines and to other fixed fuel systems supplying
liquid-fuelled appliances such as diesel heaters. Further
requirements relating to appliances and their installation and
maintenance are also included in this chapter. If you carry
spare fuel in portable containers, the requirements related to the
safe type and location of spare fuel containers is also
covered.
An important
preface
on the nature of
…
…
petrol
Petrol is very volatile, that is, it evaporates
quickly generating highly flammable vapours. A small spill of petrol
will create a large amount of vapour. Likewise, when it is being
transferred and especially when a tank is being filled and the
vapour in the ‘empty’ tank is displaced by the liquid fuel. Even if
the concentration of vapour is too rich to burn immediately, it will
dilute to flammable or explosive levels, even though given enough
ventilation, it may dissipate to a safe level eventually. Petrol
vapour is three to four times heavier than air. It will sink to the
lowest level of its surroundings, accumulating at low level in
places such as unventilated lockers and bilges or in enclosed spaces
such as the cabins and cockpits of boats.
…diesel
As with petrol, diesel as a liquid does not burn, but
when it is heated, the vapour given off is combustible and will burn
strongly. To reach this stage, termed the flash point, diesel fuel
only needs to be heated to around 56°C and this can be lower in
winter due to the anti-waxing additives. Diesel can be raised to
flash point temperature by contact with gas flames, frictional
sparks, electric sparks, and small fires as well as other heat
sources. Diesel fuel will ignite readily; materials soaked through
with diesel and acting as a wick, greatly assist the spread of an
established fire. Once alight, diesel burns with great heat
and strength.
Fuel System
Maintenance
A diesel fuel system is a miracle o f modern technology. It must meter quantities of fuel as
small as a few millionths of a gallon, raise this to a pressure as
high as 5,000 psi, and inject it into the engine at a moment in
time. Given the close tolerances in the machining of all fuel
injection pumps and injectors, a minuscule piece of dirt can do
extensive damage. If right from the start the owner gets rid of dirt
and water in the fuel, then 90 percent of potential engine problems
can be avoided.
"Give a diesel engine clean fuel and it will run
forever." This is less of an exaggeration than you might
think.
Repair statistics show that 90% of diesel
engine problems stem from contaminated fuel. The promise of
eliminating 9 out of 10 potential failures should put fuel-system
maintenance at the top of your list.
Start With Clean Fuel
Don't make your task more difficult by taking on
contaminated fuel. The bad things that happen to diesel fuel inside
your tank also occur inside the supplier's storage tanks. That isn't
a problem for you if the fuel is efficiently filtered on the way to
the nozzle. If you have any doubts about the cleanliness of the fuel,
pump some into a clean glass jar and let it sit a few minutes. Water
and dirt will settle to the bottom. If you see either, filter the
fuel before it goes into the tank, or better yet, buy your fuel
somewhere else!
Keep Out Water
Petrol engines can ingest a certain amount of water
with the fuel without serious consequences, but if a single droplet
of water in diesel fuel makes it all the way to the cylinder, the
sudden steaming of the water can blow the tip right off an injector.
This is the reason for having a water-separating filter, but too
much water in the fuel can overwhelm this filter.
If you took aboard dry fuel, shouldn't
it stay dry inside your tank? No. Contaminated fuel is only one way
water gets into the fuel aboard boats. It also leaks in around the
fill cap, it is occasionally driven in through a flooded vent
fitting, and it forms inside the tank as condensation.
Leaking Fill
Caps
By far the most common cause of
contaminated boat tanks are deck fill caps that leak. Most of these
things are stupidly m ounted
flat on decks which may puddle with water. The cap has a tiny little
O-ring that is supposed to seal and keep water out. DOES IT? I
wouldn't depend on one of these things unless I could prove that it
doesn't leak. Check the condition of the o-ring and weather it is
sealing. One way to check positively is to clean the o-ring seat
thoroughly; next apply some black or any colour paint to the o-ring
and screw the cap in place, tight. Then remove it and see if the
paint has been completely transferred to the ring seat. If not, you
now know where the problem is.
Another problem is the simple failure to seat the
cap fully after refuelling. This actually happens a lot, so check to
see if the cap is loose. Side-deck deck-fills, especially on
sailboats, can spend a lot of time under water and are often the
primary source of water contamination. If the cap's seal isn't
airtight, replace the gasket or the fitting.
The Tank
Vent
Improperly located fuel tank vent
fittings are one of the top causes of water getting into tanks. When
this is the cause, if you are a salt water boater, then it will be
salt water in your tank. A fuel tank vent fitting on the side of the
hull should be angled down and aft ward. If angled in any other
direction, you've got a problem that needs fixing. Watch out for
deteriorated plastic and zinc alloy fittings; some of these things
deteriorate incredibly fast. The vent line should have a riser loop
on the inside. That is, it travels upward first, then downward. If
not, that is another potential problem.
Where is the tank's vent fitting? If it is on the
side of the hull, deep heeling or heavy rolling might submerge it,
admitting water into the tank. If it is through the transom, a
following sea might drive water back into the tank. Even when it is
located in the cockpit or on the cabin side an errant wave might
engulf it. Water also condenses out of the air inside the tank. Due
to the daily heating/cooling cycle, a small amount of moisture will
condense out of the air every day. The more air in the tank,
the more potential for condensation, so it is a good idea to keep
tanks topped off, especially while the boat is not being used.
Prevent
Algae
Like mold on bread, algae and fungi can thrive
inside fuel tanks. These microbes require both fuel and water, so
the drier the fuel, the smaller your algae problem is likely to be.
However, keeping all water out of the fuel is improbable, so diesel
fuel should always be treated with a biocide to prevent the growth
of microbes. Avoid products that contain alcohol, which attacks
O-rings and other rubber parts in the fuel system.
Tank Care 
No matter how meticulous you are about the fuel
you take aboard, dirt, water, and microbes-dead or alive-accumulate
in the bottom of the tank over time. They may seem harmless enough
just lying there, but the first time you are motoring in bumpy
conditions, they get churned up and find their way to the fuel
pick-up, either in small amounts or in big gulps. If you are lucky,
this contamination simply plugs your primary filter and starves the
engine of fuel until it dies-hopefully not at some critical moment.
If you are unlucky, some of this debris finds a way past the filters
and damages the injector pump or the engine. It is advisable to
clean out the tank periodically. How often depends on fuel quality
and even tank material, but every couple of years you should at
least draw some fuel from the very bottom of the tank to check for
water and/or sediment. You cannot do this through the pick-up tube
feeding the engine because it is an inch or so above the bottom. If
the tank doesn't have a drain fitting or a clean-out port, you will
need to find some other way to get a suction hose to the bottom.
Mobile services are also available that draw all the fuel out of
your tank and circulate it through a filtration system. This is
known as "polishing" the fuel, and done properly it removes the
majority of the sediment from the tank.
Deterioration
Most permanent fuel tanks are housed deep in the
bilge where rapid changes in temperatures cause a fair amount of
sweating on the tank exterior and condensation inside. The fuel
filter and water separator will remove the internal condensation,
but the exterior of the tank relies on air moving through the bilge
to keep its surfaces dry. Welded edges on metal tanks are
susceptible to crevice corrosion. Threaded and welded fittings for
draw and fill lines are other trouble spots. Unfortunately,
a metal tank’s weakest links are the undersides and outboard side,
which are difficult and in some cases impossible to see.
Another troublesome situation is when a metal fuel tank is encased
in foam. The idea is the foam will help anchor the tank in place and
insulate it from moisture. In reality, the opposite is true and over
time vibration and movement cause the foam to separate from the
metal. The expansion serves as a gateway for moisture to wick its
way between the foam and the tank where it often is trapped.
Bottom line is that if your boat is more than 10 years old
and the fuel tank installation is similar to the scenario described
above, you need to take a long hard look at its condition sooner
rather than later.
Fuel
Lines
Proper fuel lines last a long time, but improper
lines can shed internally and contribute to fuel contamination.
Metal fuel lines are less susceptible to chemical deterioration, but
the supply line connected to the engine must never be metal because
movement and vibration will eventually cause the rigid line to
crack. Flexible hose is unaffected by vibration and ideal for boat
use. Vent and fill hoses should exhibit an uninterrupted
drop to the tank; any dip that allows fuel to stand risks hose
deterioration and fuel contamination.
Filters
There is a reason that the fuel filter mounted on a
diesel engine is called the secondary filter. The engine
manufacturer expects this filter to deal only with contamination
small enough to have passed through the primary filter.
Every diesel engine must have both a primary and a
secondary filter, and the primary filter must remove water
from the fuel. I prefer a primary filter with a clear sediment bowl
(although, if this is not a fire resistant type it can cause
problems with passing BSS examinations), which should be
inspected daily. Water in the bowl is visible evidence of water in
the tank. If you need to drain the bowl (it has a plug just for this
function) more often than every 100 engine hours, the tank needs
cleaning.
Filters should be changed when they are dirty, but
unless your primary filter is fitted with a vacuum gauge (which
reveals the extent of restriction), you will need to change the
element at some regular engine-hours interval. Your engine manual
should specify. In recognition that the primary filter captures most
of the contaminants, it is a common and generally acceptable
practice to change the secondary filter element at every other
primary filter change.

Note: For boats using the Norfolk
Broads- East Anglia, the long delayed Boat Safety Scheme will be
imposed on all private craft starting from April 2007.
The following Fuel System Installation
standards have been taken from the original BSS Technical Manual
with adjustments made to include changes made since the introduction
of the revised BSS Checking Procedures 2-April 20005.
Therefore boats obliged to
meet BSS requirements will need to comply with the
following:
- All permanently installed fuel
systems and fixed engines must be designed, installed and
maintained in a way that minimises the risks of explosion, or of
fire starting or spreading.
- Fuel filling arrangements must
prevent any overflow from entering the interior of the
vessel.
- All fuel filling points must
clearly identify the fuel in use.
- Marking must be provided to
identify the location of fuel system emergency shut-off devices,
or their means of operation, which are not in open view.
- All permanently installed fuel
systems must be designed, installed and maintained to ensure
fuel-tight integrity.
- All permanently installed fuel
tanks and fuel system connections must be accessible for
inspection.
- The pressure systems of
steam-powered installations must have a current inspection
certificate issued by a recognised competent
person.
|
Filling
Pipes
Filling pipes shall be
taken to deck level or so arranged as to ensure that any fuel
overflowing will not be discharged into any part of the vessel
including the bilges. |
Objective
The objective of this standard is to
avoid any accumulation of fuel inside a boat as a result of
overfilling the fuel tank. Whether the cause is overfilling,
blockages, restrictions or blowbacks, there is a risk that fuel
could find its way into the interior of the boat if its fuel-filling
points have no means of preventing this. A small amount of leaked
fuel can contribute to the cause or a spread of a fire. Leaked
petrol could cause an explosion. This is the risk being addressed in
this section.
Installation &
Design
The objective, which is particularly
pertinent when tanks are out of sight of the person carrying out the
filling operation, can be achieved if the filler cap is positioned
so that: (see example images below).
The camber of the deck will cause
any overflow to discharge overboard
A coaming high enough to prevent
spillages reaching the interior of the vessel is fitted
A diverter arrangement is fitted
around the filler cap

The position of the filling connection and the
camber (slope) of the deck may be such that fuel overflowing can
still be discharged into the vessel even though the filler pipe is
taken to deck level, therefore installing the filler pipe to deck
level is not, by itself, sufficient. Preventing overflowing fuel
from entering any part of the vessel takes precedence over the
installation of the filling pipe to deck level.
Unseen spillage
The design must ensure that there is no risk of
unseen spillage during fueling operations.
Notes – This requirement
does not apply to the following provided there is no risk of unseen
spillage:
historic (i.e. bone fide
ex-working boat) diesel-engined narrowboats;
diesel tanks, of up to a maximum
capacity of 27l (6gal)
Open vessels, such as RIBs (Rigid Inflatable Boats)
with a continuous deck or sole that is fuel tight to the interior of
the vessel and bilge spaces, meet this requirement. Diesel fuel
fillers onto self-draining cockpits meet this requirement if they
have…
a continuous deck or sole;
and,
drain outlets above the normal
laden waterline; and,
are fuel tight to the
interior of the vessel, including bilge
spaces.
|
Fuel filling
installations
The filling pipe shall
have an internal diameter of at least 31.5mm (1 1/4”)and any
flexible hose shall be of non-kinking material suitable for
the fuel used, and must be connected with leak proof joints
between the top of the tank and a screw cap or plate forming
the filling connection.
Deck filling connections
shall be outside the coaming.
All flexible hoses shall
be adequately supported and of minimum practicable length,
with all joints or connections ready
accessible. |
Objective
The objective of this standard is to ensure that
fuel can be safely loaded onto the boat without blowback and
spillage and that the fuel filling system is free of
leaks.
Accessibility
Its good installation practice that all joints and
connections are ready accessible. This means they must be capable of
being reached for inspection, removal or maintenance without the
removal of permanent craft structure but it may be necessary to use
tools or remove access panels or remove any items of portable
equipment stowed in places intended for storage of portable
equipment in order to gain access.
| Example
image : As can be seen in this picture below, good
access is available for regular inspections to the filler
pipe, (noticeable in the background) and to the vent
pipe (in the fore-ground) and to the feed and return
connections.(adjacent the diesel heaters fuel shut-off
cock). |
F illing pipe
The internal diameter of the filling pipe should be
at least 31.5mm throughout its length.
The outside diameter of this pipe would be
approximately 50mm.
If the pipe has a diameter less than this “blowback”
of fuel could occur or the filling nozzle may not enter
properly.
Non Kinking pipes
It is important that the bore of the pipe cannot
become restricted either by design or by accident.
A non-kinking pipe will prevent the walls of the
pipe from collapsing and thus restricting the bore when it is
necessary for the pipe to be bent at an angle or any object comes
into accidental contact with the pipe.
Check that the flexible filling pipe cannot be
compressed by squeezing it by hand.
Is the fuel filling line self-draining so that fuel
is not retained and is it free of kinks or other
restrictions?
This is an upgraded standard introduced in April
2005: Fuel filling lines must be ‘self-draining’ i.e. fall
continuously from the filling point to the fuel tank connection so
that fuel is not retained. Fuel filling lines must not be kinked or
restricted.
Damaged or deteriorating fuel filling lines could
fail and result in a leak that could form a potential fire,
explosion, or pollution hazard depending on the fuel used. In the
case of petrol, hose not designed specifically for that fuel can
fail rapidly. Indeed all fuel oils can ‘attack’ unsuitable
materials.
Filling pipes-suitability for fuel
The material of the pipe must not be unduly permeable to the fuel used or react
chemically with the fuel leading to deterioration and leaks.
In use, the material must be resistant to damage
deterioration resulting in corrosion, hardening, brittleness,
shrinkage and cracking. Any localised or undue softening of flexible
hoses may be a sign of an adverse reaction affecting the inner wall
which has not yet reached the outer layers.
Fuel filling hose must be marked as suitable for the
fuel in use or supported by an appropriate declaration.
Note: However since April 2005 – diesel
filling hose in good condition may be accepted without marking
or declaration provided it can be examined over its entire length.
Enough suitably marked diesel filling hose, or enough petrol hose,
must be accessible to make a reasonable assessment as to the hose’s
general condition.
It is not a requirement under the BSS for diesel
filler hose to be fire resistant but it is strongly
recommended.
| Example image
above : This petrol filling
hose was found on a Broads hire cruiser and was not
considered fire retardant or suitable for any type of fuel
never mind petrol, and definitely fails the standard.
|
Best Practice: We
recommend that you use hoses marked with BS EN ISO 7840 although
hoses marked with SAE J 1527, DIN 4798 or marked with the type of
fuel in use are acceptable. We recommend the use of double clamps on
a filling hose used for petrol.
Metal Filling pipes must be examined carefully to
ensure that the pipe and its connections show no signs of cracking
or slackness etc caused by metal fatigue due to
vibration.
|
Deck and fuel filling
connections
All deck and fuel
filling connections shall be situated as to minimise the risk
of cross contamination and shall be clearly marked on the deck
fittings or immediately beside then indicating the purpose of
each connection and, in the case of fuel connections, the
exact type of fuel. |
Objective
The objective of this standard is to prevent fuels
being incorrectly loaded and contacting systems and components which
are not suitable.
Cross contamination
Cross contamination may be prevented by:
Separating the connections by
approximately 250mm
Camber of a deck carrying any
overflow overboard
Installing a divertor arrangement
around the connection
Use of deck fitting caps which
require different keys to open them.
Marking of deck connections
The purpose of each deck connection shall be clearly
labelled/marked. This marking is to be either on the fitting, or cap
or immediately beside it. Fuel connections must be marked with the
exact type of fuel used. The label can be made of plastic, (but not
embossed tape) and can be painted on.
Connections marked with the word FUEL or GAS are not
acceptable.
Filling and discharge points may be marked with the
internationally accepted symbol (eg ISO 11192 and
ISO8099).
Clearly marked
Clearly marked means that the marking is in direct
view of any person using the connection.
It is recommended that lettering is:
A minimum of 5mm high
Clearly distinguishable from its
background
Not removable by abrasion or
contact
Cannot become illegible through
cleaning or normal use
The specific fuel type in use must be correctly and
clearly marked on or adjacent to all fuel filling
points:
‘DIESEL’; or ‘FUEL OIL’, or ‘GAS OIL’, or ‘DERV’, or
‘BIODESEL’; or, ‘PETROL’, or ‘GASOLINE’; or; ‘LPG BUTANE/PROPANE’ as
appropriate; or, ‘PARAFFIN’; or, ‘PETROIL’.
Best practice
We recommend that other disused deck connections, if
not blanked off, also be marked clearly to prevent cross
contamination and spillage.
Note – Unused fuel filling
points must be permanently disabled to such an extent that it would
require the use of tools to remove the disabling method. The use of
a suitable proprietary adhesive to secure filling point caps or
plugs in place etc. meets this requirement.
|
Vent
pipes
A vent pipe of minimum
practicable length with an internal diameter of not less than
12mm shall be fitted at the highest point of every fuel tank
and connected with leak proof joints.
The material used shall
be non kinking and suitable for use with the fuel
concerned. |
The objective of this standard is to ensure that
fuel tanks are effectively vented to prevent over and under pressure
and blow backs during filling operations. Potentially dangerous and
polluting fuel blow-backs are known to happen during refilling. The
tank also needs to be able to ‘breathe’ to help the supply of fuel
to the engine or appliance. Temperature changes cause the volume of
fuel to expand and contract.
Venting needs to be effective at all levels of fuel
in the tank. A vent line can also be a filling line, or an overflow
line, and the requirement for a vent does not apply to small
auxiliary tanks with a vented filling cap on the tank.
Minimum practical length
The vent pipe is required to extend to a height
equal to or greater than the level of the filling
connection.
It may be necessary to incorporate an inverted “U”
bend or swan’s neck in the pipe to prevent ingress of water and
debris which could result in contamination of the fuel or blockage
of the vent pipe.
Note – where the filling point is mounted on
a deck a swan neck in the vent line to the underside of the deck
meets this requirement.
| Example image:
As can been seen in this
picture the vent pipe exits directly through the topsides
without swan necking up to deck level. This was common on
older vessels and as with this installation (good access
available) it will not be expensive or time consuming to
bring up to standard. See the image below for the correct
installation, although the vent pipe should be clipped/secured
to the underside of the deck to be 100%
correct. |
If fuel were retained in the pipe it
would no longer act as a vent pipe as there would be no clear
passage for the air venting from the tank. The category would also
change to that of a fuel pipe permanently charged with
fuel.
The route taken by a flexible vent pipe is to take
into account of anything which may damage the pipe e.g. heat sources
and the need for access to the connections.
Vent pipe installation
In general, every fuel tank must have an
individual and separate vent line. However, a vent is not required
where day tanks are fitted with an overflow pipe which returns fuel
back to the main storage tank. The hole in the filler cap of small
capacity tanks of no more than 27 litres is deemed to meet this
requirement. Examples include those found on Stuart Turner petrol
tanks, Yanmar engines’ close-coupled tanks or diesel tanks supplying
appliances.
Vent lines must be connected to the top of the tank
and be ‘selfdraining’, i.e. fall continuously from the vent outlet
to the tank, or, where a swan neck is installed, from the top of the
swan neck down to the vent outlet and the fuel tank
connection.
On tanks over 27 litres visually check that the vent
is:
Above filling point level,
and
Provided with a flame arrestor,
and
Has a minimum internal diameter of
9.5mm
Best practice
However, we recommend fitting a vent line of at
least 12mm (1/2 in) internal diameter fitted which meets with
international standards.
Notes – The internal
diameter may be verified by measuring the outside diameter and
estimating wall thickness. The following are approximate
indications, copper 11.5mm (1/2 in), steel 12.5mm (1/2 in), hose
15.5mm (5/8 in).
Location of vent pipe on the tank
The vent pipe is to be fitted at the highest point
of the fuel tank to minimise the risk of creating a space at the top
of the tank where fuel vapour could accumulate.
Leak proof joints
Visually and manually check vent pipes for leaking
fuel at joints.
Flexible hose used as a vent pipe
It is important that the bore of the pipe cannot
become restricted either by design or by accident. A non kinking
pipe will prevent the walls of the pipe from collapsing and thus
restricting the bore when the hose is bent or any object comes into
accidental contact with the pipe.
Vent pipe suitability
This standard has been recently adjusted, and since
April 2005 Diesel tank vent hose (not petrol) in good condition may
be accepted without marking or declaration provided it can be
examined over its entire length. However we highly recommend
suitability is determined by the long-term performance of the pipe
and its condition in use, and we suggest the material of the pipe
should not be unduly permeable to the fuel used nor react chemically
with the fuel leading to deterioration and leaks.
We suggest the material should be resistant to
damage and deterioration resulting in corrosion, hardening,
brittleness, shrinkage and cracking and any localised or undue
softening of flexible hoses may be a sign of an adverse reaction
affecting the inner wall which has not yet reached the outer
layers.
| Example image:
After a recent change from a
petrol to diesel engine installation this vent pipe has
been adapted to receive the diesel engines fuel return line.
(to save fitting a connection to the tank). The return line
will need to be re-routed and secured at 500mm intervals
to be deemed as
acceptable. |
Best practice
We recommend that you use hoses marked with BS EN
ISO 7840 although hoses marked with SAE J 1527, DIN 4798 or marked
with the type of fuel in use are acceptable.
Unmarked pipes
Petrol filling pipes which are not marked but
supported by a declaration of suitability from the manufacturer,
supplier or boat builder are acceptable. Examiners may also accept
petrol filling hose which they recognise as being
compliant.
Metal vent pipes must be examined carefully to
ensure that the pipe and its connections show no signs of
deterioration or slackness. Soldered joints may be used but their
use is not encouraged.
|
Vent pipe outlets and
flame arrestors
Vent pipe outlets shall
be fitted in a position where no danger will be incurred from
escaping fuel or vapour.
Each opening shall be
furnished with an effective wire gauze diaphragm flame
arrestor of non-corrosive
material |

The objective of this standard is to ensure that any
vapours emerging from the vent opening do not give rise to an
explosion hazard. Fuel vapours exhaust from the vent. If ignited, a
flame close to, or at the end of, the vent line, has the potential
to flash back into the fuel tank. An unprotected vent outlet could
become blocked by debris or insects, etc.
Danger from escaping fuel or vapour
It is important, and good safety practice
to ensure that the vent pipes terminal is not in a position where
there is a risk of danger. The international standard recommends
that the vent pipe terminals be in the open air and at least 400mm
from any ventilation openings where vapour may enter enclosed cabin
spaces. Vent pipe terminals must also be clear of any potential
source of ignition and 400mm is an appropriate guideline for a
minium separation.
Diesel, paraffin or other fuel-oils escaping onto a
source of ignition would create a fire hazard. There is even greater
risk with petrol as the vent will exhaust highly flammable vapours
regularly.
Flame arresters
It is fundamental marine engineering practice to
install a flame arrester on the outlet of all vent pipes. This
device prevents the passage of flame by means of small openings,
convoluted flame paths or by ensuring that the temperature of the
side which is not exposed to flame does not reach a high enough
temperature to ignite a flammable vapour mix.
In the UK it has been historically recommended
practice to install a copper or brass gauze with a mesh size of 28
wires per inch. However, the ISO does not have any recommendation
for gauze size and requires only that an effective flame arrestor is
fitted. For the purpose of the BSS therefore any proprietary flame
arrestor will be accepted.
What ever type of flame arrestor is used it is
important to ensure that the openings in the flame arrestor body do
not restrict the passage of either by design or by blockage with
dirt or corrosion etc.
Where the flame arrester is not of a suitable
proprietary type the openings in the arrester’s body must be at
least of the same area as the cross-sectional area of the vent
line.
Notes – Flame arresters not
recognised as proprietary must be supported by satisfactory
documentation. The hole in the top in the filler cap as provided by
the original engine or fuel tank manufacturer, on tanks no more than
27 litres (6 gal) capacity, is compliant.
|
Fuel
tanks
Fuel tanks shall be
properly secured and be installed as low as practicable and
shall be constructed of a suitable non-corrosive
material.
Materials used in the
construction of fuel tanks shall have a fire resistance of 30
minutes in accordance with BS 476: Part
20.
Tanks shall have
sustained a pressure test of 0.25Kgf/cm2 (no longer
mandatory). |
The objective of this standard is to ensure that
fuel tanks are manufactured to give adequate protection to their
contents in normal use or in the event of an accident.
This section considers the vulnerability of fuel
tanks to leaks or failures that can lead to fuel and/or fuel vapour
building up in the interior of the boat. It also covers the
potential for chemical reaction between the fuel used and the tank
material. The final concern is the fuel tank’s fire resistance which
can help prevent a major escalation of a small fire close to the
tank. Any stress in your boat’s fuel tank, lines, or fittings,
caused by movement in the system, could lead to a persistent or even
catastrophic fuel leak.
Security
Fuel tanks which are not an integral part of the
hull must be properly secured to prevent any movement which could
result in:
Damage to the structure of the
tank
Damage to the associated pipework
and fittings.
Tanks must be secured by: metal framework; brackets;
straps; welding to the hull; or collision chocks.
Joints and seams
Soft soldered fillers must not be used since they
would inevitably fail when exposed to excessive heat e.g. in a fire
situation.
Installation height
If the fuel tank is installed in the position
determined by the boat builder it will be accepted that it complies
with this standard. This applies if the boat was built by the
owner.
There must be no obvious signs that any
modifications have been carried out. The main indications that this
may have occurred are that the additions and/alterations do not
match the manufactures specification for:
Colour
Construction grade
Marking (name, model, consumer
info etc)
Mismatch of name, materials, and
connections
Materials
Suitable materials must be used for the construction
of the fuel tanks since fuel tanks must be resistant to corrosion.
Choosing the wrong material for a boat’s tank, could introduce
weakness and/or poor fire resistance. Unsuitable types of materials
may be susceptible to corrosion and/or chemical reaction with the
fuel inside. The wrong material may not be strong enough or may not
have the right durability to prevent permeation or cracking. Failure
could lead to fuel or fuel vapour building up unnoticed within the
confines of your boat.
|
Example image: This fuel tank pictured above was
installed in a Sealine F43 (year 2000) ocean going motor
cruiser. It was constructed from Aluminium. It had a
manufacturers label fixed and clearly visible, and was date
tagged and pressure tested to 5 PSI. The filler pipe, vent
arrangement, securing devices and associated
connections had all been competently installed under the RCD
regulations introduced in 1998 (EU) and which run in line with
the BSS standards. (great example, with the remote fuel shut
off cock noticeable in the
fore-ground). |
Plastic tanks
CE marked plastic tanks are accepted provided they
are used within any restrictions placed on their use by the
manufacturer. The requirements for marking of the fuel
and the test procedure apply to these tanks. A separate information
sheet is available on application to the BSS office www.boatsafetyscheme.com
.
Notes – Examiners are not
required to identify whether fuel tanks are lined or otherwise
internally coated. A judgement will be made on suitability from a
visual assessment of the tank’s external surfaces. If
inaccessibility prevents a general assessment of the fuel tank
material, it is ‘not verifiable’, and will be considered as
non-compliant until the suitability of the material can be
verified.
Notes – Particular attention
should be paid to areas under dipsticks/sounding pipes for evidence
of damage from dipstick ‘bounce’, where these are
accessible.
Visually and manually check for material of tank for
suitability and metrical failure such as:
Corrosion
Heavy flaking
Deep pitting
Fuel seepage
|
Example Images:
Welded
edges on metal tanks are susceptible to crevice corrosion.
Threaded and welded fittings for draw and fill lines are other
trouble spots. Unfortunately, a metal tank’s weakest link is
its undersides and outboard side, which are difficult and in
some cases impossible to see. This tank, although not leaking,
is ready for replacement! The plastic tank, above left was
fine and properly CE marked, there was however a leak at the
filling pipe position which will require further
investigation. (see pooling diesel around the
rim). |
Fire resistance
The international standard BS EN ISO 10088 does not
make any recommendation for fire resistance of fuel tanks with
exception of non-metallic petrol tanks which must meet a fire test
of 2 ½ mins followed by a pressure test.
Close riveted joints and seams
Joints and seams made by close riveting must be
suitably sealed by hard soldering or brazing or other means to make
the joint fuel tight and fire resistant.
Tank pressure test
(not BSS mandatory for vessels manufactured prior to
16 June 1998).
This exemption only applies to the pressure test and
not to any other requirements for fuel tanks e.g. non-corrosive
material or fire resistance.
The international standard lowers the required tank
pressure test from the previous UK recommendation of 0.25 Kgf/cm2 to
0.2 Kgf/cm2.
Accessibility of fuel tanks and
connections
It is not necessary for the tank to be accessible
for removal or maintenance but it is necessary for at least part of
the tank to be capable of being reached for inspection.
If inaccessibility prevents a general assessment of
the fuel tank material, it is ‘not verifiable’, and will be
considered as non-compliant until the suitability of the material
can be verified.
Accessibility of tank connections
It is a requirement of this standard ands it is also
good installation practice that all connections are ready accessible
for inspection.
However it is acceptable for connections to be
accessible and not ready accessible. (I.e. behind screwed down
inspection panels etc). This means that they must be capable of
being reached for inspection without removal of permanent craft
structure but it may be necessary to use tools.
The principal connections to fuel tanks are: filling
pipes; fuel take off pipe; fuel return pipe; vent pipe; drain plugs
or cocks; fuel level indicators; balance pipes (diesel engines
only).
Petrol and
Paraffin tank installation
No petrol or paraffin
tank of more than 2.5 litres (½ gallon) shall be installed
within one metre (39 ½”) of any engine or heating appliance
unless it is insulated and protected by an efficient baffle of
fire resistant material. ( April 2005 adjustments made to this
standard. Petrol tanks must be at least 100mm (4 in) from
general heat sources and at least 250mm (10 in) from a dry
exhaust. If the distances are less than those prescribed a
fire-resistant baffle in good condition must protect the tank
from radiated heat.) Measure the distance from any petrol tank
to any engine, exhaust system or other heat
source. |
The objective of this standard is to ensure that
petrol and paraffin tanks are protected against the effects of
overheating and the production of excessive amounts of
vapour.
Petrol tanks placed near an engine or heating
appliance run the risk of generating flammable vapours and the
potential for fire or explosion.
Heat shield baffles
The purpose of a baffle in this context is to
protect the fuel tank from directly radiated heat. They may be
constructed from any material which is inherently fire resistant or
which has been treated to be fire resistant.
Suitable materials would have a fire resistance of
30 minutes in accordance with BS 476; such as sheet metal of min
thickness 0.9mm; or fibre glass of approx 5mm thickness.
If timber or ply was used it must be faced with
metal or treated in such a way that it would provide the same degree
of fire resistance.
Modifications
The baffle may be modified to allow for the routing
of pipes and cables etc providing the baffle, cables and pipes meet
all the requirement standards.
BS EN ISO 10088
The international standard has changed previous UK
recommended practice of separation between a petrol tank and an
engine from one metre to 100mm (4”) and this latter distance will be
accepted for the purpose of the BSS. However, max separation between
a petrol tank and a source of heat is considered to be best
practice.
The international standard does remove the lower
limit on tank size and this change has also been adopted.
|
Fuel level indicators
Glass or plastic fuel sight tube gauges should
not be used. Fuel
level indicators, if fitted, shall be of a type which does not
allow escape of fuel vapour in the event of damage to the
indicator. |
The objective of this standard is to ensure that
fuel level indicators are properly installed so as to minimise the
risk of the loss of the contents of the fuel tank in the event of
damage. An inappropriately installed gauge on your tank could
introduce a serious weakness. Glass or plastic
fuel-sight tube gauges can easily be damaged by knocks or the heat from a fire, leading to a complete loss of
the tank contents. With diesel or paraffin tanks, limiting any
potential fuel escape is key to maintaining
protection.
Fuel gauges- column sight tube
For many years the use of plastic or glass fuel
sight tube gauges was not recommended practice in the UK as they
were felt to be breakable, required a joint at or near the base of
the tank, were exposed to physical damage and breached the fire
resistance requirements of the tank.
This applied to all gauges of this type including
those which are not errantly charged with fuel i.e. fuel is only
admitted to the sight tube by means of a cock or valve for the
purpose of taking a reading.
However, BS EN ISO 10088 allows their use on
diesel tanks only provided that they are protected against
physical damage and that damage does not lead to the loss of the
contents of the tank. This is achieved by the use of a shield or
cage, or by robust design, and by the incorporation of self closing
valves which means that the gauge is only open to the tank when the
operator is in attendance at the gauge.
Disconnection
Where a sight tube gauge has been disconnected to
comply with this standard, the tank outlet must be fitted with a
plug which;
Is connected to the tank by a leak proof connection
Cannot be opened accidentally
Cannot be used without the use of
tools
(note that the self-closing valve at the top is not
required if the gauge connection is made to the
top of the tank)
Petrol tanks must not be fitted with glass or
plastic tube or strip-type fuel gauges.
Escape of fuel or vapour. Transparent
covers
Gauges covered with a transparent cover for the
purpose of reading a dial or indicator are only acceptable if no
fuel has leaked into the space behind the cover.
If fuel can be seen behind the cover, the gauge
becomes a glass or plastic sight tube gauge which is not
permitted.
Note – Self-closing valves
are not required for fuel gauges on any diesel fuelled vessel
formerly used for the commercial carriage of freight or passengers
or as a tug or as an icebreaker and which is to be licensed for use
as a pleasure vessel, or registered for use as a houseboat, unless
used for the purposes of hire or reward. Documentary evidence of
former use addressed to the BSS manager is required to enjoy this
exception.
Note – loose or damaged
gauge needles, or other such level-indicators, mounted behind any
glass or transparent cover do not constitute
non-compliance.
Dipsticks
Fitted dipsticks may be attached to the fuel filler
cap, or separate fitting, provided they comply with these
standards.
Calibration
Dipsticks, when fitted shall be calibrated by means
of marks, numbers, or letters etched or engraved into the
surface.
|
Bonding of fuel tanks
Tanks shall be effectively bonded by low resistance
metallic conductors of adequate strength to their deck filling
connection, and in the case of non-conducting deck or hull,
tanks shall be electrically bonded to an earth point in direct
electrical contact with the surrounding water, for discharge
of static electricity. |
The objective of this standard is to ens ure
that petrol filling and tank systems are electrically bonded to
prevent the build up of static charge which may lead to an ignition
hazard. This section addresses the hazards related to static charges
and petrol vapours. The build-up of static
charge, from fuel flowing through the filling pipe could result in
sparks, which in turn could ignite petrol vapour.
Note: The international
standard restricts this requirement to petrol systems against the
wish of the UK to see it retained for all fuel systems. Bonding of
diesel systems is therefore recommended as good practice. (but not a
BSS failure).
Bonding to deck filling connections
The bonding to the deck filling connection must be:
effective and by a low resistance metallic conductor of adequate
strength. An effective bond is made when a conductor of the correct
grade is securely fitted between the tank and the deck
connection.
The recommended grade is a heavy duty cable with a
conductor of at least 2.5mm Sq.
Where the filling pipe is made of conducting
material it is not necessary to provide additional metallic
conductor between the tank and the filling connection.
Checking
There must be:
No movement at any of the connections
No sign of damage, deterioration, or
corrosion in the cable or its connections.
Note – all necessary
electrical bonding connections must be seen or reached in order to
be able to establish the existence of adequate bonding
provision.
Bonding to an earth point
The standard does not specify the size of this
earthing point and the BMEA Code of Practice recommends that the
resistance to ground be less than 10 ohms.
Minimum size
No minimum size is specified for the cable
connecting the fuel tank to an earthing point but note the
recommended size (2.5mm Sq) for the cable used for bonding the tank
to a deck filling connection.
|
Fuel tank
drainage
Tanks may be drained
only by a suitable drain valve fitted with a plug on the
outlet. |
The objection of this standard is to ensure that
fuel tanks can be drained in a controlled way and that drains are
protected against unintended operation. Leaking fuel from a poor
connection or an unsuitable pipe is a hazard. If there is a fire,
the system must be resistant to the heat and flames. It is known
that fuel can leak past tank drains which are worn, or which have
not been properly closed.
Example image
| This drain tap was noticeably leaking and will
require capping off with a suitable 'tools to
remove' plug. |

Drain valves-fittings
It is not a requirement that a drain valve must
be fitted and it is not a fault if there is no valve. However,
if a valve is fitted it must be suitable.
Drain valves-suitability
If a drain valve is fitted it must be connected to
the tank by a leak proof connection and fitted with a plug
which:
Cannot be accidentally opened
Cannot be removed without the use of
tools
If a drain tap or cock is used, the outlet must be
sealed with a plug which cannot be removed without the use of
tools.
|
Fuel
supply
The fuel supply shall be
drawn through the top of the tank or as near to the top of the
tank as is practicable by means of an internal pipe extending
to near the bottom of the tank.
In the case only of
gravity feed systems a feed from a cock or valve directly
screwed in near the bottom of the tank is
permitted.
Any return fuel line
required to be connected to the tank shall be connected
through the top of the tank or as near to the top as is
practicable. |
The objective of this standard is to ensure that the
risk of the loss of the contents of a fuel tank is minimised in the
event that any fuel pipe is damaged.
Connection of fuel supply line
It has previously been UK recommended practice to
ensure all connections to fuel tanks are made at the top of the
tank. The intention behind this recommendation was to minimise the
risk of the loss of the contents of the tank in the event that the
fuel pipe was damaged downstream. This is particularly hazardous in
the case of petrol tanks.
However, BS EN ISO 10088 gives further options in
the case of diesel fuel systems. In these types of installations the
connection of the fuel feed can be made below the top of the tank or
the highest point on the sides or end of the tank provided
that:
Either the connection is protected by a valve
Or the connection is welded to the tank and
the feed pipe reaches a point above the top of the
tank.
Connections to petrol tanks must be made at the top
of the tank.
For gravity fed systems, petrol or diesel, where the
fuel supply has to be drawn through the bottom of the tank it must
be drawn through a cock or valve screwed directly attached to the
tank.
Practicability
Providing it is installed as near the top of the
tank as possible, the fuel supply may be drawn through the side of
the tank if there is insufficient room to install a take-off fitting
and associated pipe work at the top of the tank.
Note – A gravity-fed petrol
installation is one where there is no lift-pump to move the fuel
from the tank to the engine and the height of the tank is above that
of the engine.
Best practice We
recommend/suggest that diesel fuel feed or return lines are drawn
through the top of the tank, or as near to the
top of the tank as is practical.
Return fuel lines
The purpose of fitting the return fuel pipe to the
top of the tank is to avoid the loss of the tanks contents if the
return pipe or its fittings and connections develop a leak or are
damaged. Therefore the options that apply to fuel feed systems apply
here.
This check only applies to installations where the
return fuel line is connected to the tank. It does not apply to
systems where it returns fuel to some other part of the fuel
installation e.g. it is connected to the fuel filter.
Return fuel lines must not discharge direct into the
engine compartment or bilge. Return lines are only found on diesel
engine vessels and petrol engines with fuel injection
systems.
Notes – If any tank
connections or tank valves are inaccessible for inspection and the
condition is ‘not verifiable’, they will be classified as
non-compliant until their condition can be verified as acceptable.
This requirement applies to all tank connections and valves,
including fuel filling lines, vent lines and balance
pipes.
|
Fuel pipes, balance
pipes and valves
All fixed fuel feeds and
pipes permanently charged with fuel shall be made of softened
copper, stainless steel, aluminium alloy, or (diesel
installations only) mild steel of suitable size, fixed clear
of exhaust systems and heating apparatus and adequately
supported to minimise vibration and
strain.
Ballance pipes are only
permitted in diesel fuel installations.
Any balance pipe between
fuel tanks must comply with the requirements of this standard
and must in addition be fitted with valves directly attached
to the tank and so construction that the valves will not
become slack when
operated. |
The objective of this standard is to ensure that
fuel pipes and hoses are manufactured of appropriate materials and
are installed to prevent damage in normal use. It is also intended
to specify particular requirements for balance pipes in diesel
systems to minimise the risk of the loss of the contents of the
tanks in the event of damage.
Fuel Pipe Material
All fixed fuel feeds and fuel pipes permantley
charged with fuel are to be made of the materials listed above as:
They do not react with the fuel. (the hose in the
picture on the left has reacted with the fuel and will require
replacement).
The risk of damage and deteriration to fuel
pipes is mininised.
Softened copper pipe is solid drawn copper pipe
which has been annealed (heated) after the
drawing process which makes it more suitable for bending and working
than hard drawn pipes.
Flexible Tubing
Flexible tubing is more vulnerable to damage and the
effects of heat than rigid pipework and its use for pipes
permanently charged with fuel is a balance between convenience and
replacement costs. It must be expected that a flexible hose will
need replacement a number of times through out the lifetime of the
boat.
Example image
| As can be seen in the image on the right, a
corroded flexible armoured type fuel hose ready for
replacement. The newer correct BS ISO 7840 fire resistant
(yellow coloured) fuel hose is
adjacent |
The material of any hose must not react chemically
with the fuel in use leading to deterioration and leaks as in this
case.
Flexible hose is widely used for connections to
engines in order to mitigate the effects of vibration when the
engine is running, and to take into account of the relative movement
between different parts of the boats structure.
Existing engines may be fitted with hose to BS MA
102 which is acceptable providing the hose is in good condition. If
the condition of the hose is suspect, they must be replaced with
hoses which meet at least the fire resisting quality of BS EN ISO
7840.
Balance Pipes
Flexible balance pipes are allowed providing the
installation meets the requirements of the appropriate
Standard.
Spill Racks
Spill racks must comply with the fire
resisting quality requirements of BS EN 7840 and be connected with
efficient joints.
Soft soldered connections and unclipped push-on
joints must not be used.
The requirement is consistent with the international
standard for marine diesel engines for small craft IOS
16147.
Note: Supplementary
information on spill rail options is available on
www.boatsafetyscheme.com or by post or email from the BSS Office.
Injector leak-off hoses fitted by the manufacturer within an
enclosure on the engine meet this requirement.
Example image
|
These PVC push on
pipes must not be used. They can be replaced with either a
solid metallic spill rail or replace them with BS EN ISO 7840
hose and small hose clamps. |
Checking
Identify pipes and hoses permanently charged with
fuel and visually and manually check for signs of:
Damage
Corrosion or
deterioration
Protection of fuel pipes
Sources of heat: Fuel pipes
are to be fixed clear of exhaust systems and heating apparatus. The
recommended clearnace is 125mm but where this cannot be achieved, a
clearnace of 75mm is considered tha absoulte minimum.
Routing: In routing pipes
clear of sources of heat, care must be taken to ensure that they are
not exposed to risk of mechanical damage. It may be necessary to
provide shielding or protection if both risks cannot be
eliminated.
Checking
Visually check route of pipes and hoses for
clearance from unshielded or unlagged exhaust systems. Where
clearance is less than 75mm check for damage to fuel system. Note:
that the failure point is on damage not distance.
Example image
As can be seen in the picture a fuel pipe is almost
touching a hot exhaust pipe on this Eperspacher warm air diesel
heater. The exhaust should be properly lagged (they get very hot)
and the fuel pipe re-routed away from the exhaust.
THIS PAGE IS STILL UNDER CONSTRUCTION AND
THE REMAINING BSS REQUIREMENTS FOR FUEL SYSTEMS WILL BE
INCLUDED SHORTLY
Surveying East Anglia & the
Norfolk Broads.
|